OMEGA SERIES

OMEGA SERIES

SHIELD Omega is a versatile range of open protocol fire alarm control panels compatible with existing SHIELD Omega fire alarm panel technology.

Available with one or two detection loops for a total of 250 primary points or 400 points using subpoints. SHIELD Omega uses leading edge microprocessor based electronics to provide a flexible control system with high reliability and integrity. Suitable for all small to medium sized fire detection systems, SHIELD Omega control panels can be expanded and networked to become part of much larger systems if the need arises, therefore providing a future proof solution for any installation.

With its large graphical display and ergonomic button and indicator layout, the SHIELD Omega control panel is simple and straight forward to understand for installers, commissioning engineers and end users.

Model SA-P4LR is not available now. SHIELD is manufacturing model number SA-P20R0 only. Loop Expansion Module for additional Two Loops for SA-P20R Panel, UL Listed, Model: SA-LM2

 

UL 864 9th Edition listed.

Multi-Loop 2 Analog Addressable Loops Field upgradable to 4.

126 primary points per loop.

Powerful, network wide cause and effects (500 total) 

Fully user programmable by point or zone.

800 points per panel when using devices with sub-points.

Up to 3048 m wiring length on SLC loop.

64 Panels on a network.

Programmable through a PC connection to the panel, or through keypad.

Programmable relays – 5.

Supervised Powered Outputs – 3.

4 Programmable notification appliance

Power per NAC: 1.6 A maximum.

Programmable outputs on SLC loop.

Programmable Function button on front display.

Fire Drill button on front display.

Day and night sensitivity settings (user programmable).

Power Supply: 5.25 A regulated & integrated.

LCD Display: 8x40.

Zonal Mode: Annunciation by zone w/o individual relationships.

Panel Ring Modes: Common, Zonal, and Stage 2.

NAC Outputs programmable.

Continuous, March, Temporal.

Program cause and effects AND, OR, or any two (Cross Zone).

Battery size: Up to 17 Ah in standard enclosure; up to 52 Ah with external cabinet.

Access levels: 3.

Access key switch: Yes.

Recognized for use in High Rise Buildings.

One-man walk test – Fire Test Mode.

Available in Red.

IP30.