TR-PULL-SA-TRIGA (TRIGA)
Addressable Single Action and Dual Action Pull Stations
The TR-PULL-SA is a single action pull station requiring
only one motion to activate the station. The TR-PULL-DA is a dual action pull
station requiring two motions to active the station. Both pull stations are
designed to work with Triga series fire alarm control panels (FACPs).
INSTALLATION
The TR-PULL-SA and TR-PULL-DA can be surface mounted to an SB-I/O surface back
box or semi-flush mounted on a standard single-gang with a minimum depth of
2.13”(5.40 cm) or double gang or 4” (10.61 cm) square electrical box. You can
also use the optional trim ring if the station is being semi-flush mounted.
COMPATIBILITY
The TR-PULL-SA and TR-PULL-DA are compatible with the following Triga Series
FACPs:
• TR-2100R / TR-2100B
• TR-2100ECSR / TR-2100ECSB
• TR-R2100R / TR-R2100B
·
Installer
can open station without causing an alarm condition
·
Dual-color
LED is visible through handle of station blinks green to indicate normal
operation and remains steady red in an alarm condition
·
Key
operated test and reset lock using lock plate actuator
·
Key
matches compatible FACP locks
·
Meets
ADA requirement for 5 lbs maximum pull force to active
·
Meets
the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls
and operating mechanisms guidelines (Section 4.1.3[13])
·
Shell,
door, and handle molded from durable LEXAN ®
·
Reliable
analog communications for trouble-free operation
·
Braille
text on station handle
·
Rotary
address switches for fast installation
·
Handle
latches in down position and the word Activated appears, clearly indicating the
station has been pulled
·
UL
Listed, including UL 38, Standard of Manually Actuated Signaling System